Working Time : 09:00 - 18:00
  • +994124898416

    Contact number

  • office@marinets.az

    Have a question?

Working Time : 09:00 - 18:00
  • +994124898416

    Contact number

  • office@marinets.az

    Have a Question?

Products / MTU / Diesel Engines for Generator Drivers / Continuous /Peak applications

Continuous /Peak applications

Perfect for any Business

Diesel Engines for Generator Drivers List

Continuous /Peak applications

Diesel engines for Continuous/Peak applications - 50 Hz - 1500 rpm

Continuous Power (3A)

Continuous Power ratings apply to installations where one or several generator sets serve as utility. At constant or varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: power stations

Engine model kWm kVA1) kWe1) Cooling variant
12V 2000 G65 515 575 460 A2A
12V 2000 G65 515 575 460 W2A
16V 2000 G65 655 740 592 A2A
16V 2000 G65 655 740 592 W2A
12V 2000 B26F 665 750 600 A2A
16V 2000 B26F 709 800 640 A2A
18V 2000 G65 720 810 648 A2A
18V 2000 G65 720 810 648 W2A
18V 2000 B26F 887 1000 800 A2A
12V 4000 G63 1310 1480 1184 W2A
16V 4000 G63 1635 1875 1500 W2A
20V 4000 G63 2000 2275 1820 W2A
20V 4000 G63L 2200 2500 2000 W2A



Continuous Power (3B)

Prime Power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: construction sites, remote areas

Engine model kWm kVA1) kWe1) Cooling variant
6R 1600 G10S 284 313 250 A2A
6R 1600 G20S 312 344 275 A2A
8V 1600 G10S 371 413 330 A2A
8V 1600 G20S 408 456 365 A2A
10V 1600 G10S 465 519 415 A2A
10V 1600 G20S 511 563 450 A2A
12V 1600 G10S 561 625 500 A2A
12V 1600 G20S 608 688 550 A2A
12V 2000 G45 710 800 640 A2A
12V 2000 G45 710 800 640 W2A
16V 2000 G56S 809 919 735 W2A
12V 2000 G85 810 919 735 A2A
12V 2000 G85 810 919 735 W2A
12V 2000 G16S 716 813 650 W2A
12V 2000 G26S 810 919 735 W2A
12V 2000 G36S 898 1019 815 W2A
16V 2000 G45 915 1038 830 A2A
16V 2000 G45 915 1038 830 W2A
16V 2000 G26S 998 1138 910 W2A
16V 2000 G85 1010 1156 925 A2A
16V 2000 G85 1010 1156 925 W2A
12V 4000 G73(2) 1105 1250 1000 W2A
18V 2000 G85 1191 1375 1100 A2A
18V 2000 G85 1191 1375 1100 W2A
16V 4000 G73(2) 1390 1575 1260 W2A
12V 4000 G43 1520 1750 1400 W2A
12V 4000 G83 1736 2000 1600 W2A
16V 4000 G43 2020 2313 1850 W2A
16V 4000 G83 2280 2625 2100 W2A
20V 4000 G43 2490 2875 2300 W2A
20V 4000 G83 2740 3188 2550 W2A
20V 4000 G83L 3010 3500 2800 W2A



Grid Stability Power (3G)

Grid Stability Power ratings apply to installations operating in support of utility networks or grids (especially when renewable power sources are used). At constant or varying load, the number of generator set operating hours is limited to 1000 hours per year. Full power output is available for 500 hours non-stop operation per year. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: peak shaving, grid stability and capacity programs

Engine model kWm kVA1) kWe1) Cooling variant
16V 2000 G26F 890 1000 800 A2A
18V 2000 G26F 1102 1250 1000 A2A
12V 4000 G23 1420 1600 1280 W2A
12V 4000 G63 1575 1800 1440 W2A
16V 4000 G23 1798 2100 1680 W2A
16V 4000 G63 1965 2250 1800 W2A
20V 4000 G23 2200 2500 2000 W2A
20V 4000 G63 2420 2800 2240 W2A
20V 4000 G63L 2590 3000 2400 W2A



Prime Power limited (3C)

Prime Power limited ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is limited to 1000 hours per year. A 10% overload capacity is available.
Main usage: peak shaving, grid stability

Engine model kWm kVA1) kWe1) Cooling variant
6R 1600 G40F 249 275 220 A2A
6R 1600 G50F 274 300 240 A2A
8V 1600 G40F 325 365 292 A2A
8V 1600 G50F 358 400 320 A2A
10V 1600 G40F 407 450 360 A2A
10V 1600 G50F 448 500 400 A2A
12V 1600 G40F 524 590 472 A2A
12V 1600 G50F 576 650 520 A2A

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is applied for calculation and serves
as guideline only.


Diesel engines for Continuous/Peak applications - 60 Hz - 1800 rpm

Continuous Power (3A)

Continuous Power ratings apply to installations where one or several generator sets serve as utility. At constant or varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: power stations

Engine model kWm kVA1) kWe1) Cooling variant
12V 4000 G73(2) 870 988 790 W2A
16V 4000 G73(2) 1140 1300 1040 W2A
12V 4000 G43 1190 1375 1100 W2A
12V 4000 G83 1420 1625 1300 W2A
16V 4000 G43 1680 1875 1500 W2A
16V 4000 G83 1950 2219 1775 W2A
20V 4000 G83 2290 2625 2100 W2A
20V 4000 G83L 2490 2875 2300 W2A



Prime Power (3B)

Prime Power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: construction sites, remote areas

Engine model kWm kVA1) kWe1) Cooling variant
6R 1600 G10S 284 313 250 A2A
6R 1600 G20S 312 344 275 A2A
8V 1600 G10S 371 413 330 A2A
8V 1600 G20S 408 456 365 A2A
10V 1600 G10S 465 519 415 A2A
10V 1600 G20S 511 563 450 A2A
12V 1600 G10S 561 625 500 A2A
12V 1600 G20S 608 688 550 A2A
12V 2000 G45 710 800 640 A2A
12V 2000 G45 710 800 640 W2A
16V 2000 G56S 809 919 735 W2A
12V 2000 G85 810 919 735 A2A
12V 2000 G85 810 919 735 W2A
12V 2000 G16S 716 813 650 W2A
12V 2000 G26S 810 919 735 W2A
12V 2000 G36S 898 1019 815 W2A
16V 2000 G45 915 1038 830 A2A
16V 2000 G45 915 1038 830 W2A
16V 2000 G26S 998 1138 910 W2A
16V 2000 G85 1010 1156 925 A2A
16V 2000 G85 1010 1156 925 W2A
12V 4000 G73(2) 1105 1250 1000 W2A
18V 2000 G85 1191 1375 1100 A2A
18V 2000 G85 1191 1375 1100 W2A
16V 4000 G73(2) 1390 1575 1260 W2A
12V 4000 G43 1520 1750 1400 W2A
12V 4000 G83 1736 2000 1600 W2A
16V 4000 G43 2020 2313 1850 W2A
16V 4000 G83 2280 2625 2100 W2A
20V 4000 G43 2490 2875 2300 W2A
20V 4000 G83 2740 3188 2550 W2A
20V 4000 G83L 3010 3500 2800 W2A



Grid Stability Power (3G)

Grid Stability Power ratings apply to installations operating in support of utility networks or grids (especially when renewable power sources are used). At constant or varying load, the number of generator set operating hours is limited to 1000 hours per year. Full power output is available for 500 hours non-stop operation per year. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: peak shaving, grid stability and capacity programs

Engine model kWm kVA1) kWe1) Cooling variant
12V 2000 G26S 810 919 735 W2A
16V 2000 G26S 998 1138 910 W2A
12V 4000 G43 1520 1750 1400 W2A
12V 4000 G83 1736 2000 1600 W2A
16V 4000 G43 2020 2313 1850 W2A
16V 4000 G83 2280 2625 2100 W2A
20V 4000 G43 2490 2875 2300 W2A
20V 4000 G83 2740 3188 2550 W2A
20V 4000 G83L 3010 3500 2800 W2A

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is applied for calculation and serves
as guideline only.
2) 4000 G73 with 1200 rpm




Diesel engines for Continuous/Peak applications - switchable 50/60 Hz - 1500/1800 rpm

Continuous Power (3A)

Continuous Power ratings apply to installations where one or several generator sets serve as utility. At constant or varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: power stations

Engine model kWm
(50/60 Hz)
kVA1)
(50/60 Hz)
kWe1)
(50 / 60 Hz)
Cooling variant
12V 4000 G63 / G83 2) 1310 / 1420 1485 / 1625 1188 / 1300 W2A
16V 4000 G63 / G83 2) 1635 / 1950 1865 / 2219 1492 / 1775 W2A



Prime Power (3B)

Prime Power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: construction sites, remote areas

Engine model kWm
(50/60 Hz)
kVA1)
(50/60 Hz)
kWe1)
(50 / 60 Hz)
Cooling variant
6R 1600 B30S 249 / 284 275 / 313 220 / 250 A2A
6R 1600 B40S 274 / 312 300 / 344 240 / 275 A2A
8V 1600 B30S 325 / 371 365 / 413 292 / 330 A2A
8V 1600 B40S 358 / 408 400 / 456 320 / 365 A2A
10V 1600 B40S 448 / 511 450 / 519 360 / 415 A2A
12V 1600 B30S 524 / 561 500 / 563 400 / 450 A2A
12V 1600 B40S 576 / 608 590 / 625 472 / 500 A2A
12V 2000 B76 709 / 716 800 / 813 640 / 650 A2A
16V 2000 B76 890 / 998 1000 / 1138 800 / 910 A2A
18V 2000 B76 1102 / 1097 1250 / 1250 1000 / 1000 A2A
12V 4000 G23 / G43 2) 1420 / 1520 1600 / 1750 1280 / 1400 W2A
12V 4000 G63 / G83 2) 1575 / 1736 1800 / 2000 1440 / 1600 W2A
16V 4000 G23 / G43 2) 1798 / 2020 2100 / 2313 1680 / 1850 W2A
16V 4000 G63 / G83 2) 1965 / 2280 2250 / 2625 1800 / 2100 W2A

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is applied for calculation and serves
as guideline only.
2) Available on request