Data Center Continuous Power ratings apply to data center
installations where a reliable utility power is available and comply
with Uptime Institute Tier III and IV requirements. At constant or
varying load, the number of generator set operating hours is
unlimited. Quoted ratings are in accordance with ISO 3046 and are
capable of 10% overload.
Typical applications: data centers
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
16V 2000 G26F | 890 | 1000 | 800 | A2A |
18V 2000 G26F | 1102 | 1250 | 1000 | A2A |
12V 4000G23 | 1420 | 1600 | 1280 | W2A |
12V 4000G63 | 1575 | 1800 | 1440 | W2A |
16V 4000G23 | 1798 | 2100 | 1680 | W2A |
16V 4000G63 | 1965 | 2250 | 1800 | W2A |
20V 4000G23 | 2200 | 2500 | 2000 | W2A |
20V 4000G63 | 2420 | 2800 | 2240 | W2A |
20V 4000G63L | 2590 | 3000 | 2400 | W2A |
Mission Critical Power ratings apply
to installations served by a reliable utility source. The
ratings are applicable to varying loads for the duration of a
power outage. Quoted ratings are in accordance with ISO 3046 and
are capable of 10% overload.
Typical applications: public and governmental buildings /
infrastructure, hospitals, storm avoidance programs
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
16V 2000 G26F | 890 | 1000 | 800 | A2A |
18V 2000 G26F | 1102 | 1250 | 1000 | A2A |
12V 4000G23 | 1420 | 1600 | 1280 | W2A |
12V 4000G63 | 1575 | 1800 | 1440 | W2A |
16V 4000G23 | 1798 | 2100 | 1680 | W2A |
16V 4000G63 | 1965 | 2250 | 1800 | W2A |
20V 4000G23 | 2200 | 2500 | 2000 | W2A |
20V 4000G63 | 2420 | 2800 | 2240 | W2A |
20V 4000G63L | 2590 | 3000 | 2400 | W2A |
NPP Standby Power ratings apply to
installations in thermal power stations. At constant or varying
load, the number of generator set operating hours is unlimited.
Quoted ratings are in accordance with ISO 3046 and are capable
of 10% overload. Products are qualified in accordance with IEEE
and / or KTA requirements.
Typical applications: nuclear thermal power plants or nuclear
research facilities
Engine model | kWm | kVA1) | kWe1) | Cooling variant | Spec Sheets |
---|---|---|---|---|---|
12V 4000 E63(2), (3) | 1560 | 1800 | 1440 | W2A | project specific data |
16V 4000 E63(2), (3) | 2080 | 2400 | 1920 | W2A | project specific data |
20V 4000 E63(3) | 2600 | 3000 | 2400 | W2A | project specific data |
12V 956 TB34(2) | 3900 | 4400 | 3520 | W2A | project specific data |
16V 956 TB34(2) | 5200 | 5820 | 4656 | W2A | project specific data |
20V 956 TB34 | 6500 | 7275 | 5820 | W2A | project specific data |
1) The quoted typical kVA / kWe ratings are based on typical
generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is
applied for calculation and serves
as guideline only.
2) Available on request
3) With KTA or IEEE qualifications
Data Center Continuous Power
ratings apply to data center installations where a reliable
utility power is available and comply with Uptime Institute
Tier III and IV requirements. At constant or varying load,
the number of generator set operating hours is unlimited.
Quoted ratings are in accordance with ISO 3046 and are
capable of 10% overload.
Typical applications: data centers
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
12V 2000 G26S | 810 | 919 | 735 | W2A |
16V 2000 G26S | 998 | 1138 | 910 | W2A |
12V 4000 G43 | 1520 | 1750 | 1400 | W2A |
12V 4000 G83 | 1736 | 2000 | 1600 | W2A |
16V 4000 G43 | 2020 | 2313 | 1850 | W2A |
16V 4000 G83 | 2280 | 2625 | 2100 | W2A |
20V 4000 G43 | 2490 | 2875 | 2300 | W2A |
20V 4000 G83 | 2740 | 3188 | 2550 | W2A |
20V 4000 G83L | 3010 | 3500 | 2800 | W2A |
Mission Critical Power ratings apply
to installations served by a reliable utility source. The
ratings are applicable to varying loads for the duration of a
power outage. Quoted ratings are in accordance with ISO 3046 and
represent maximum power.
Typical applications: public and governmental buildings /
infrastructure, hospitals, storm avoidance programs
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
12V 2000 G76S | 890 | 1000 | 800 | W2A |
16V 2000 G76S | 1097 | 1250 | 1000 | W2A |
16V 2000 G86S | 1371 | 1563 | 1250 | W2A |
12V 4000 G43 | 1736 | 2000 | 1600 | W2A |
12V 4000 G83 | 1910 | 2188 | 1750 | W2A |
16V 4000 G43 | 2280 | 2625 | 2100 | W2A |
16V 4000 G83 | 2500 | 2875 | 2300 | W2A |
16V 4000 G83L | 2740 | 3172 | 2500 | W2A |
20V 4000 G43 | 2740 | 3172 | 2500 | W2A |
20V 4000 G83 | 3010 | 3500 | 2800 | W2A |
20V 4000 G83L | 3490 | 4063 | 3250 | W2A |
NPP Standby Power ratings apply to
installations in thermal power stations. At constant or varying
load, the number of generator set operating hours is unlimited.
Quoted ratings are in accordance with ISO 3046 and are capable
of 10% overload. Products are qualified in accordance with IEEE
and / or KTA requirements.
Typical applications: nuclear thermal power plants or nuclear
research facilities
Engine model | kWm | kVA1) | kWe1) | Cooling variant | Spec Sheets |
---|---|---|---|---|---|
12V 4000 E83(2), (3) | 1560 | 1800 | 1440 | W2A | project specific data |
16V 4000 E83(2), (3) | 2080 | 2400 | 1920 | W2A | project specific data |
20V 4000 E83(3) | 2600 | 3000 | 2400 | W2A | project specific data |
1) The quoted typical kVA / kWe ratings are based on typical
generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is
applied for calculation and serves
as guideline only.
2) Available on request
3) With KTA or IEEE qualifications