Standby Power ratings apply to installations served by a reliable
utility source. The standby ratings are applicable to varying loads
for the duration of a power outage. Quoted ratings are in accordance
with ISO 3046 and represent maximum power.
Typical applications: industrial and manufacturing plants,
residential areas, healthcare and hospitals, airports
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
6R 1600 G70F | 274 | 300 | 240 | A2A |
6R 1600 G80F | 301 | 330 | 264 | A2A |
8V 1600 G70F | 358 | 400 | 320 | A2A |
8V 1600 G80F | 394 | 440 | 352 | A2A |
10V 1600 G70F | 448 | 500 | 400 | A2A |
10V 1600 G80F | 493 | 550 | 440 | A2A |
12V 1600 G70F | 576 | 650 | 520 | A2A |
12V 1600 G80F | 634 | 715 | 572 | A2A |
12V 2000 G25 | 635 | 715 | 572 | A2A |
12V 2000 G25 | 635 | 715 | 572 | W2A |
12V 2000 G76F | 732 | 825 | 660 | A2A |
12V 2000 G65 | 765 | 860 | 688 | A2A |
12V 2000 G65 | 765 | 860 | 688 | W2A |
12V 2000 G86F | 887 | 1000 | 800 | A2A |
16V 2000 G25 | 890 | 1000 | 800 | A2A |
16V 2000 G25 | 890 | 1000 | 800 | W2A |
16V 2000 G65 | 975 | 1100 | 880 | A2A |
16V 2000 G65 | 975 | 1100 | 880 | W2A |
16V 2000 G76F | 979 | 1110 | 888 | A2A |
18V 2000 G65 | 1100 | 1250 | 1000 | A2A |
16V 2000 G86F | 1100 | 1250 | 1000 | A2A |
18V 2000 G65 | 1100 | 1250 | 1000 | W2A |
18V 2000 G76F | 1235 | 1400 | 1120 | A2A |
12V 4000 G23 | 1575 | 1800 | 1440 | W2A |
12V 4000 G63 | 1750 | 2000 | 1600 | W2A |
16V 4000 G23 | 1965 | 2250 | 1800 | W2A |
16V 4000 G63 | 2185 | 2500 | 2000 | W2A |
20V 4000 G23 | 2420 | 2800 | 2240 | W2A |
20V 4000 G63 | 2670 | 3100 | 2480 | W2A |
20V 4000 G63L | 2850 | 3300 | 2640 | W2A |
Standby Power with Overload
ratings apply to installations served by a reliable utility
source. The standby ratings are applicable to varying loads for
the duration of a power outage. Quoted ratings are in accordance
with ISO 3046 and are capable of 10% overload.
Typical applications: industrial and manufacturing plants,
residential areas, healthcare and hospitals, airports
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
12V 2000G16F | 665 | 750 | 600 | A2A |
12V 2000G26F | 709 | 800 | 640 | A2A |
16V 2000G16F | 806 | 910 | 728 | A2A |
16V 2000G26F | 890 | 1000 | 800 | A2A |
16V 2000G36F | 1000 | 1135 | 908 | A2A |
18V 2000G26F | 1102 | 1250 | 1000 | A2A |
12V 4000G23 | 1420 | 1600 | 1280 | W2A |
12V 4000G63 | 1575 | 1800 | 1440 | W2A |
16V 4000G23 | 1798 | 2100 | 1680 | W2A |
16V 4000G63 | 1965 | 2250 | 1800 | W2A |
20V 4000G23 | 2200 | 2500 | 2000 | W2A |
20V 4000G63 | 2420 | 2800 | 2240 | W2A |
20V 4000G63L | 2590 | 3000 | 2400 | W2A |
1) The quoted typical kVA / kWe ratings are based on typical
generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is
applied for calculation and serves
as guideline only.
Standby Power ratings apply to
installations served by a reliable utility source. The
standby ratings are applicable to varying loads for the
duration of a power outage. Quoted ratings are in accordance
with ISO 3046 and represent maximum power.
Typical applications: industrial and manufacturing plants,
residential areas, healthcare and hospitals, airports
Engine model | kWm | kVA1) | kWe1) | Cooling variant |
---|---|---|---|---|
6R 1600 G70S | 312 | 344 | 275 | A2A |
6R 1600 G80S | 343 | 375 | 300 | A2A |
8V 1600 G70S | 408 | 456 | 365 | A2A |
8V 1600 G80S | 448 | 500 | 400 | A2A |
10V 1600 G70S | 511 | 563 | 450 | A2A |
10V 1600 G80S | 561 | 625 | 500 | A2A |
12V 1600 G70S | 613 | 688 | 550 | A2A |
12V 1600 G80S | 668 | 750 | 600 | A2A |
12V 2000 G45 | 780 | 888 | 710 | A2A |
12V 2000 G45 | 780 | 888 | 710 | W2A |
12V 2000 G85 | 890 | 1000 | 800 | A2A |
12V 2000 G85 | 890 | 1000 | 800 | W2A |
12V 2000 G76S | 890 | 1000 | 800 | W2A |
12V 2000 G86S | 987 | 1125 | 900 | W2A |
16V 2000 G45 | 1010 | 1156 | 925 | A2A |
16V 2000 G45 | 1010 | 1156 | 925 | W2A |
16V 2000 G76S | 1097 | 1250 | 1000 | W2A |
16V 2000 G85 | 1115 | 1250 | 1000 | A2A |
16V 2000 G85 | 1115 | 1250 | 1000 | W2A |
18V 2000 G85 | 1310 | 1500 | 1200 | A2A |
18V 2000 G85 | 1310 | 1500 | 1200 | W2A |
16V 2000 G86S | 1371 | 1563 | 1250 | W2A |
18V 2000 G76S | 1371 | 1563 | 1250 | A2A |
12V 4000 G43 | 1736 | 2000 | 1600 | W2A |
12V 4000 G83 | 1910 | 2188 | 1750 | W2A |
16V 4000 G43 | 2280 | 2625 | 2100 | W2A |
16V 4000 G83 | 2500 | 2875 | 2300 | W2A |
16V 4000 G83L | 2740 | 3125 | 2500 | W2A |
20V 4000 G43 | 2740 | 3125 | 2500 | W2A |
20V 4000 G83 | 3010 | 3500 | 2800 | W2A |
20V 4000 G83L | 3490 | 4063 | 3250 | W2A |
1) The quoted typical kVA / kWe ratings are based on typical
generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is
applied for calculation and serves
as guideline only.
Standby Power ratings apply to
installations served by a reliable utility source. The
standby ratings are applicable to varying loads for the
duration of a power outage. Quoted ratings are in accordance
with ISO 3046 and represent maximum power.
Typical applications: industrial and manufacturing plants,
residential areas, healthcare and hospitals, airports
Engine model | kWm (50/60 Hz) |
kVA1) (50/60 Hz) |
kWe1) (50 / 60 Hz) |
Cooling variant |
---|---|---|---|---|
12V 4000 G23 / G43 2) | 1575 / 1736 | 1800 / 2000 | 1440 / 1600 | W2A |
12V 4000 G63 / G83 2) | 1750 / 1910 | 2000 / 2188 | 1600 / 1750 | W2A |
16V 4000 G23 / G43 2) | 1965 / 2280 | 2250 / 2625 | 1800 / 2100 | W2A |
16V 4000 G63 / G83 2) | 2185 / 2500 | 2500 / 2875 | 2000 / 2300 | W2A |
1) The quoted typical kVA / kWe ratings are based on typical
generator efficiencies.
The kVA figures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efficiency is
applied for calculation and serves
as guideline only.
2) Available on request